DGT Series
|
DGT4 - 4-CHANNEL WEIGHT TRANSMITTER
|
DGT4 - 4-CHANNEL WEIGHT TRANSMITTER
|
|
|
|
|
| | | | FUNCTIONS AND DATA AVAILABLE VIA FIELDBUS |
- NET, GROSS and TARE weight
- DIGITAL INPUTS status
- RELAY OUTPUTS status
- SETPOINT setting
- Alibi memory writing and reading (optional)
- Weight status (eg positive, negative, stable, unstable)
- Error conditions (eg overload, underload) - Calibration - SETUP configuration
- Diagnostics of each converter channel
The integrated WEB SERVER allows complete diagnostics, calibration and remote configuration of the weight transmitter from ethernet network.
Only for PROFINET, ETHERNET IP and MODBUS TCP models.
- UL certificated version
- Special programs according to customer specifications
- Kit for legal for trade approval
|
|
|
4-channel weight transmitter for weight transfer to PLC via fieldbus, analog output or RS485. It allows the reading and diagnostics of each load cell or each connected scale (up to 4).
Available versions: PROFINET I/O | ETHERNET IP | ETHERCAT | MODBUS TCP | DEVICENET | PROFIBUS | ANALOG OUTPUT | RS485
Approvals: CE-M EN 45501, OIML R-76, OIML R-61 (MID), OIML R-51 (MID), Australian approval
Integrated WebServer as standard
| | | | - Power supply: 12-24Vdc
- Converter: A/D 24 bit with 4 channel
- Max scale number: 4
- Load cells connection: with 4 or 6 wires (with sense)
- Operating modes:
- Digital junction box - Multi-scale transmitter
- Conversion rate: up to 3200 conv./sec
- Selectable sampling rate: up to 400 conv./sec
- Displaying: up to 800.000d
- Signal sensitivity: 0,03 µV/d (0,03 µV/e)
- Resolution: 3.000.000 points
- Linearization: up to 8 points
- Connectable load cells: up to 8 350 Ω cells
- BUS: depending on the model (See version chart)
- Serial ports:
- 1 RS232 for configuration from PC with "Dinitools®" - 1 RS485 Port (Mod. DGT4 / DGT4 AN) - Analog output: 16 bit (DGT4AN Model) choosing between 4-20mA, 0-5Vdc or 0-10Vdc.
- Digital outputs: n. 2 configurable OUTPUTS
- Digital inputs: n. 2 configurable INPUTS
- Certifications:
- CE-M EN 45501 - OIML R76 (10000e o 3000 + 3000e) / R51 / R61 MID - UL Listed (upon request) - EU Type Examination Certificate (45501:2015) - Australian legal for trade certificate of approval (NMI S788) - Case: ABS, for Din bar (106 x 90 x 58 mm)
- Calibration:
- Theoretical (mV\V) - With sample weights - Remotely by WEB SERVER - From the keyboard - From PC with "Dinitools" - Keyboard functions:
- Zeroing - Tare - Function mode - Manual data printing/sending - On/Stand-by - Program functions:
- Setpoint - High resolution - Peak - Alibi Memory - Unit of measure conversion Available in 7.15 firmware version downloadable from the DOWNLOAD area: Net/Gross; Weighs totalisation; Formulation; Counting; In/Out Truck weighing and Hold.
- Keyboard: mechanical with 5 digits
- Display: 13mm red LED
|
|
|
Available versions
| Code | Description |
| DGT4 | Transmitter for DIN bar with 4 channels, 2 IN and 2 OUT. 5-key keypad, LED display, and standard weighing program. |
| DGT4AN | Transmitter for DIN bar with 4 channels, 2 IN, 2 OUT, analogue output. 5-key keypad, LED display, and standard weighing programme. |
| DGT4ETHIP | Transmitter for DIN bar with 4 channels, 2 IN, 2 OUT and EthernetIP port 5-key keypad, LED display, and standard weighing programme. |
| DGT4PRONET | 4 channel Din rail weight transmitter, with 2 IN, 2 OUT and PROFINET port. 5-key keypad, LED display. |
| DGT4PB-1 | Transmitter for DIN bar with 4 channels, 2 IN, 2 OUT, Profibus. 5-key keypad, LED display, and standard weighing programme. |
| DGT4ETHCAT | Transmitter for DIN bar with 4 channels, 2 IN, 2 OUT and EtherCAT port. 5-key keypad, LED display, and standard weighing programme. |
| DGT4DEVNET | Transmitter for DIN bar with 4 channels, 2 IN, 2 OUT and DeviceNet port. 5-key keypad, LED display, and standard weighing programme. |
| DGT4MODTCP | Transmitter for DIN bar with 4 channels, 2 IN, 2 OUT and MODBUS TCP/IP port. 5-key keypad, LED display, and standard weighing programme. |
RS485 lightning and surge protection
| Code | Description |
| RS485PDIN a> | Protection circuit for port 485, with enclosure for DIN rail installation. Protection according to IEC 1000-4-5/D (IEC 801-5/D). |
Approval for sale to third parties
| Code | Description |
| KCEM a> | Plates and Welmec form for legal trade use of a scale. NET PRICE. Service available in combination with a Dini Argeo indicator. |
| ECEM-AU | Single platform/scale legal-for-trade approval for Australia. |
Printers/Labellers
| Code | Description |
| TPRP-1 | (S1) Panel thermal printer. 5Vdc power supply (power adapter not included). Attention: connection cable kit not included, to be ordered separately. |
| 14TPRC | Connection cable kit for TPRP-1. |
| TPRPCAL | 5Vdc power supply unit. |
Clock Calendar / Alibi Memory for type-approved communication
| Code | Description |
| ALMEM-1 | (S1) Alibi memory (fiscal memory, max 120.000 weighs) for approved weight transmission to PC/PLC or data recording on MMC/USB. Built-in real time clock to print the date/time with PCB, screw terminal, plastic box and UL-marked labels.
If applicable, it requires FW 05.00.02 or higher. Not compatible with weight repeaters. |
| DFCLK | (S1) Real time clock for printing/displaying of date and time. With UL marked PCB, screw terminal, plastic box and labels (if applicable). |
Power supplier for DIN bar
| Code | Description |
| MDR2012 | 12Vdc power unit for DIN bar. 110/240Vac input. CE and UL certified. Not compatible with BOX2121S. |
| DR1512 | 12Vdc power unit for DIN bar. 110/240Vac input. |
ABS boxes for wall mounting
| Code | Description |
| BOX2121S | Wall IP65 box with transparent door. Dimensions 210x210x100 mm, equipped with 2 cable glands. Suitable for DGT1 and DGT4 series instruments. |
Communication Interfaces
| Code | Description |
| SETHDIN-1 | RS232 / RS485 / Ethernet converter. Modbus RTU / Modbus TCP/IP (if applicable). Connectable to all Dini Argeo weight indicators via the serial port. ABS housing for DIN rail. With PCB, screw terminals, plastic box and UL marked labels (if applicable). |
Options for ATEX version
| Code | Description |
| ZBA1S a> | Intrinsic protection three channel Zener barrier. Specific for connection to load cells, for mounting on DIN rail in a safe area, or in a flame-proof case. Marking: ATEX/IECEx II (1) GD [Ex ia Ga] IIC [Ex ia Da] IIIC. Provided with safety instructions and the ATEX EU declaration of conformity (EN, DE, FR, ES and IT). |
| KZBA-1 a> | ATEX ABS housing kit with Zener Barrier ZBA1S for load cells. For intrinsically safe weighing systems in a dangerous zone. Dimensions 179x359x166,5mm. Marking of housing + Zener Barrier ZBA1S: ATEX II 3(1)G Ex nA [ia Ga] IIC T4 Gc X for gas, ATEX II 3(1)D Ex tc [ia Da] IIIC T135°C Dc IP66 X for dust. Provided with safety instructions and the ATEX EU declaration of conformity (EN and IT). |
| KMB4-1 a> | Kit of 3 ATEX Zener barriers for load cells, in an ABS box. For up to 4 load cells of 350 ohm, for intrinsic protection weighing systems in a dangerous area. Marking of the whole box with three Zener barriers: ATEX II 3(1)G Ex nA [ia Ga] IIC T4 Gc (-20°C ≤ Ta ≤ +40°C) for gas, ATEX II 3(1)D Ex tb [ia Da] IIIC T130°C Dc IP65 (-20°C ≤ Ta ≤ +40°C) for dusts. Provided with safety instructions and the ATEX EU declaration of conformity (EN and IT). |
| DCATEXMB4 | ATEX declaration for the whole system with Dini Argeo Zener barriers. Ex II 2G IIC T6 Gb X e Ex II 2D IIIC T125°C Db X system, with label of the whole system, for weight indicator connected to Dini Argeo zener barriers, connected to a mechanical structure with ATEX load cells (each cell must be certified with CCATEX option). Provided with descriptive document of the assembly and ATEX EU declaration of conformity of the assembly (EN and IT). |
| JB4QA a> | ATEX equalisation box made of ABS IP67, for up to 4 cells. 4 + 1 fairleads. Marking: ATEX II 2G Ex ib IIC T6 Gb for gases, ATEX II 2D Ex tb IIIC T115°C Db IP65 for dust. Provided with safety instructions and the ATEX EU declaration of conformity (EN, DE, FR, ES and IT). |
| JB4QAI a> | ATEX equalisation box made of stainless steel IP66 for up to 4 cells. 4 + 1 fairleads. Marking: ATEX II 2G Ex ib IIC T6 Gb for gases, ATEX II 2D Ex tb IIIC T115°C Db IP65 for dusts. Provided with safety instructions and the ATEX EU declaration of conformity (EN, DE, FR, ES and IT). |
| EXCB6 | (S6) Blue shielded cable 6x0.22 mm², only for EX i (2GD) assemblies. PVC inner sheath. Tinned copper braid shielding. Polyurethane outer sheath, diameter 5.8 mm. Temperature range: -40 / +80 °C. Minimum bending radius >/= 7 x O.D. €/m |
Other options
| Code | Description |
| UMAN | Printed user manual (Free download from the website). |
| TECMAN | Printed technical manual (Free download from the website). |
| TECSUP | Technical assistance by telephone upon request. |
| ECEMDOC | Printed EU declaration of conformity, EU certificate of verification, test certificate and metrological book (free download from our website, only for approved CE-M products). NET €. |
Pdf product page
All the specifications and images can be subject to variations and upgrades without prior notice.
|
|